Conceptual Reference Database for Building Envelope Research Prev
Next

CFD model of the airflow, heat and mass transfer in cool stores

Nahora, H. B., Hoanga, M. L., Verbovena, P., Baelmansb, M. and Nicola?¡§a, B. M.
2005
International Journal of Refrigeration, 28 368-380


Nahora, H. B., Hoanga, M. L., Verbovena, P., Baelmansb, M. and Nicola?¡§a, B. M., (2005), "CFD model of the airflow, heat and mass transfer in cool stores", International Journal of Refrigeration, 28 368-380.
Abstract:
A transient three-dimensional CFD model was developed to calculate the velocity, temperature and moisture distribution in

an existing empty and loaded cool store. The dynamic behaviour of the fan and cooler was modelled. The model accounted for

turbulence by means of the standard k-3 model with standard wall profiles. The model was validated by means of velocity, air

and product temperature. An average accuracy of 22% on the velocity magnitudes inside the empty cold store was achieved and

the predicted temperature distribution was more uniform than predicted. In the loaded cold store, an average accuracy of 20%

on the velocity magnitudes was observed. The model was capable of predicting both the air and product temperature with

reasonable accuracy.


This publication in whole or part might be found online. Check the sources on the related article below. Or use search engines on the web.

Related Concepts





CRDBER, at CBS, BCEE, ENCS, Concordia,