    Essay:

    Tests on Curtain walls

    sources: http://www.efcocorp.com/efco/efco_products/L/L10/L10.1_Spec.html

    http://home.coqui.net/pprada/aecorp/specs.htm

    Test Procedures and Performance

    Air Infiltration Test

    Test unit in accordance with ASTM E 283 at a static air pressure difference of 6.24 psf.

    Air infiltration shall not exceed .06 cfm per square foot of fixed wall area

    Water Resistance Test

    Test unit in accordance with ASTM E 331.

    There shall be no uncontrolled water leakage at a static test pressure of 10.00 psf

    Dynamic Water Resistance Test

    Test unit in accordance with AAMA 501-94.

    There shall be no uncontrolled water leakage at a dynamic test pressure of 10.00 psf

    Uniform Load Deflection Test

    Test in accordance with ASTM 330-79. Architect to specify design wind pressure, both positive and negative required by the governing building code, as calculated from ANSI A58.1, or as determined by boundary layer wind tunnel testing. Use 20.00 psf as minimum.

    The system shall withstand ( ) psf positive and ( ) psf negative design wind pressure normal to the plane of the wall.

    Deflection under design load shall not exceed L/175 of the clear span or 3/4".

    Uniform Load Structural Test

    Test in accordance with ASTM 330-79 at a pressure 1.5 times the design wind pressure in 1.05.4.b.

    At conclusion of the test there shall be no glass breakage, permanent damage to fasteners, curtain wall parts, or any other damage which would cause the curtain wall to be defective.

    Condensation Resistance Test (CRF)

    Test unit in accordance with ASTM 1503.

    Condensation Resistance Factor (CRF) shall not be less than 54.

    Thermal Transmittance Test (Conductive U-Value)

    Test in accordance with ASTM 1503.

    Conductive thermal transmittance (U-Value) shall not be more than .69 BTU/hr/degree F/SF.

    The Aluminum Association, Inc. (AA)

    1. DAF-45: Designation System for Aluminum Finishes.

    2. SAS-30: Specification for Aluminum Structures.

    B. American Architectural Manufacturers Association (AAMA):

    1. 501.1: Standard Test Method for Metal Curtain Walls for Water Penetration Using Dynamic Pressure.

    2. 501.2: Field Check of Metal Curtain Walls for Water Leakage.

    3. 603.8: Voluntary Performance Requirements and Test Procedures for Pigmented Organic Coatings on Extruded Aluminum.

    4. 605.2: Voluntary Specification for High Performance Organic Coatings on Architectural Extrusions and Panels.

    5. 606.1: Voluntary Guide Specification and Inspection Methods for Integral Color Anodic Finishes for Architectural Aluminum.

    6. 607.1: Voluntary Guide Specification and Inspection Methods for Clear Anodic Finishes for Architectural Aluminum.

    7. 608.1: Voluntary Guide Specification and Inspection Methods for Electrolytically Deposited Color Anodic Finishes for Architectural Aluminum.

    8. 809.2: Voluntary Specification for Non-Drying Sealants.

    C. American National Standards Institute, Inc. (ANSI)

    1. A58.1: Building Code Requirements for Minimum Design Loads in Building and Others Structures.

    2. Z97.1: American National Standard Performance Specifications and Methods of Test for Safety Glazing Materials Used in Buildings.

    D. American Society of Testing and Materials (ASTM)

    1. A 193: Specification for Ally-Steel and Stainless Steel Bolting Materials for High Temperature Service.

    2. A 307: Specification for Carbon Steel Externally Threaded Standard Fasteners.

    3. B 209: Specification for Aluminum and Aluminum-Alloy Sheet and Plate.

    4. B 211: Specification for Aluminum and Aluminum-Alloy Bar, Rod, and Wire.

    5. B 221: Specification for Aluminum and Aluminum-Alloy Extruded Bar, Rod, Wire, Shape, and Tube.

    6. C 1036: Specification for Flat Glass.

    7. C 1048: Specification for Heat-Treated Flat Glass.

    8. E 283: Test Method for Rate of Air Leakage Through Exterior Windows, Curtain Walls, and Doors.

    9. E 330: Test Method for Structural Performance of Exterior Windows, Curtain Walls, and Doors by Uniform Static Air Pressure Difference.

    10. E 331: Test Method for Water Penetration of Exterior Windows, Curtain Walls, and Doors by Uniform Static Air Pressure Difference.

    11. E 773: Test Method for Seal Durability of Sealed Insulating Glass Units.

    12. E 774: Specification for Sealed Insulating Glass Units.

    E. Flat Glass Manufacture's Association (FGMA): Glazing Manual.

    F. Insulating Glass Certification Council (IGCC): Classification of Insulating Glass Units.

    G. U.S. Consumer Product Safety Commission (CPSC): 16 CFR 1202 Architectural Glazing Standards and Related Materials.