Airflow characteristics in the occupied zone of ventilated spaces.

Hanzawa, H., Melikow, A. K. and Fanger, P. O.
1987
ASHRAE Transactions, 93(pt 1): 524-539


Hanzawa, H., Melikow, A. K. and Fanger, P. O., (1987), "Airflow characteristics in the occupied zone of ventilated spaces.", ASHRAE Transactions, 93(pt 1): 524-539.
Abstract:
Draft is one of the most common causes of complaint in ventilated or air-conditioned spaces. Therefore, knowing the turbulent airflow in these spaces and the impact of this flow on the sensation of draft is very important. The characteristics of turbulent flow (turbulence intensity, length scales of turbulence, turbulence kinetic energy, etc. ) were investigated in 20 typically ventilated spaces. Relationships between these characteristics and the mean velocity were found. The turbulence energy spectra are similar to those in a fully developed turbulent flow. The spectra reveal the major contribution to total turbulent energy made by the larger eddies in the low-wave number range. Some of the experimental results were compared with existing numerical predictions.


Related Concepts


Author Information and Other Publications Notes
Hanzawa, H.
  1. Air turbulence and sensation of draught  
Melikow, A. K.
     
Fanger, P. O.
Technical University of Denmark, Kongens Lyngby, Denmark,
  1. Air turbulence and sensation of draught
  2. Impact of temperature and humidity on the perception of indoor air qualit
  3. Indoor air quality in the 21st century: search for excellence
  4. Subjective perceptions, symptom intensity and performance: a comparison of two independent studies, both changing similarly the pollution load in an office
  5. The impact of sorption on perceived indoor air quality.
  6. Thermal Comfort
  7. Ventilation and health in non-industrial indoor environments: report from a European Multidisciplinary Scientific Consensus Meeting (EUROVEN)  



CRDBER, at CBS, BCEE, ENCS, Concordia,