Field observations over the last two decades have shown that water infiltration through building
envelope defects and into wall assemblies can cause serious damage if water accumulates within the core
of the wall. If at high moisture content and appropriate temperature for sufficient time, wall components
such as wood framing or wood-based sheathing are vulnerable to mold growth and biodegradation.
Several hygrothermal studies have looked at large amounts of water introduced in wall assemblies.
The objective of the present study was to investigate the capacity of a wall assembly to manage small
amounts of water penetration. The work performed is experimental and includes 19 specimens grouped
into a testing hut within a large environmental chamber subjected to a series of three tests. The behavior of
three specimens during two of these tests is discussed. The paper presents the experimental protocol
including the test specimen design, the monitoring instrumentation, the two wetting methodologies used
and the environmental conditions to which the walls are subjected during the wetting and drying phases of
the experiment. One wetting method consists of injecting water according to a measured leakage rate in an
actual window/wall failure and actual rain frequency and duration extracted from a Montreal weather 20-
year database. The second method involves uniformly wetting a framing component by initial partial
immsersion. The results presented illustrate the role of different wood-based sheathings in the wetting and
drying behavior of the wall assemblies. The sheathing materials include oriented strand board, plywood
and asphalt-coated fiberboard. Moisture content and relative humidity measurements for series of
identical specimens built with different sheathing panels are presented during wetting and drying modes.
The rate of drying is compared and the role of temperature gradient is demonstrated. |